China Cable Factory

11kV Cable Specifications & Size Chart: Complete Current Rating Tables [2026]

· 26 min read· China Cable Factory

Key Takeaway

Complete 11kV cable size chart with current ratings, dimensions, and weight tables. Single-core and 3-core XLPE 6.35/11kV cable specifications per IEC 60502-2. Copper and aluminium conductor options for underground and aerial installation.

11kV XLPE insulated 3-core steel wire armoured medium voltage cable showing copper conductors, XLPE insulation layers, copper tape screen, and SWA
11kV 3×240mm² XLPE/SWA medium voltage cable — complete construction visible

Selecting the correct 11kV cable size is one of the most critical decisions in medium voltage network design. Undersized cable causes overheating, accelerated insulation ageing, and premature failure. Oversized cable wastes capital on unnecessary copper or aluminium while increasing installation difficulty due to weight and bend radius.

This reference guide provides complete specification tables for 6.35/11kV XLPE insulated cables — covering single-core and three-core configurations, copper and aluminium conductors, current ratings for all standard installation methods, physical dimensions, and weight data. All values conform to IEC 60502-2, with cross-references to BS 6622, AS/NZS 1429.1, and GB/T 12706.2 where applicable.

Whether you are sizing cable for a utility distribution feeder, an industrial incoming supply, a solar farm collection circuit, or a mining site ring main, these tables provide the engineering data needed to make correct sizing decisions without flipping through multiple manufacturer datasheets.

11kV Cable Voltage Rating Explained

The standard voltage designation for 11kV system cables is 6.35/11(12)kV or 8.7/15(17.5)kV, depending on the earthing arrangement of the network:

  • 6.35/11kV (U₀/U) — for solidly earthed or resistance-earthed systems where earth faults are cleared within 1 hour
  • 8.7/15kV (U₀/U) — for impedance-earthed or isolated neutral systems where earth faults may persist, requiring thicker insulation

Where:

  • U₀ = rated power-frequency voltage between conductor and metallic screen (earth)
  • U = rated power-frequency voltage between any two phase conductors
  • Um = maximum system voltage (12kV or 17.5kV respectively)

Most utility distribution networks worldwide (UK, Australia, Middle East, Africa, Southeast Asia) operating at a nominal 11kV use cables rated 6.35/11kV because their systems are solidly earthed with fast fault clearance. Networks with resonant earthing (Petersen coil) or isolated neutral require 8.7/15kV rated cable for the same 11kV system voltage.

The insulation thickness difference is significant: 3.4mm for 6.35/11kV versus 4.5mm for 8.7/15kV (IEC 60502-2, Table 1). This directly affects overall cable diameter, weight, and bend radius — all factors that matter during procurement and installation planning.

11kV Cable Construction Standards

All 11kV XLPE cables share a common construction principle defined by IEC 60502-2. Understanding each layer is essential for correct specification.

Cross-section of 3-core XLPE insulated steel wire armoured 11kV medium voltage cable showing copper conductors, XLPE insulation, copper tape screen, SWA armour, and PVC outer sheath
11kV 3-core XLPE/SWA cable cross-section — all construction layers visible

Layer-by-Layer Construction

LayerMaterialFunction
ConductorStranded copper (Class 2) or aluminium (Class 2)Carries load current
Conductor screenSemi-conductive XLPE compoundSmooths electric field at conductor surface
InsulationCross-linked polyethylene (XLPE)Primary dielectric barrier, rated for 90°C continuous
Insulation screenSemi-conductive XLPE compoundSmooths electric field at insulation surface
Metallic screenCopper tape (0.1mm) or copper wires (16–70mm²)Carries fault current, provides earthing path
Water barrierSwellable tape or powder (optional)Prevents longitudinal water penetration
BeddingPVC or PE compoundMechanical protection layer under armour
ArmourGalvanised steel wire (SWA) or steel tape (STA)Mechanical protection for direct burial
Outer sheathPVC (black or red) or PE/MDPEEnvironmental protection

Key Design Parameters per IEC 60502-2

Parameter6.35/11kV8.7/15kV
Insulation thickness3.4 mm4.5 mm
Conductor screen thickness≥0.5 mm≥0.5 mm
Insulation screen thickness≥0.5 mm≥0.5 mm
Max conductor temperature (continuous)90°C90°C
Max conductor temperature (short-circuit)250°C250°C
Max conductor temperature (emergency)130°C130°C
Partial discharge (max at 1.73×U₀)≤10 pC≤10 pC
Routine test voltage (5 min)21 kV26 kV

11kV Single-Core Cable Size Chart

Single-core 11kV cables are used for high-current circuits where heat dissipation requirements favour individual phase separation, for large conductor sizes above 300mm² where three-core cable becomes impractically heavy, and where single-point or cross-bonded sheath earthing can be implemented to eliminate circulating sheath currents.

Single-Core 6.35/11kV — Copper Conductor, XLPE, Copper Wire Screen, PE Sheath (Unarmoured)

Standard construction: Cu conductor (Class 2) / semi-conductive screen / XLPE insulation (3.4mm) / semi-conductive screen / copper wire screen / PE outer sheath.

Conductor Size (mm²)Conductor Diameter (mm)Insulation Thickness (mm)Screen Area (mm²)Overall Diameter (mm)Weight (kg/km)
357.23.41624.5750
508.33.41626.0920
709.93.41628.01150
9511.53.41630.01400
12012.93.41631.51650
15014.43.41633.51950
18516.03.41635.52300
24018.23.42538.52900
30020.43.42541.03400
40023.23.43544.54200
50026.03.43548.05200
63029.33.45052.56600
80033.13.45057.08300

Note: Dimensions are nominal and may vary ±5% between manufacturers. Screen area selected per IEC 60502-2 Table 7 for 1-second fault duration.

Single-Core 6.35/11kV Current Ratings — Copper Conductor (Amperes)

Current ratings below are for single-core XLPE cables with copper conductors, based on IEC 60287 calculation methods. Reference conditions: ambient air temperature 40°C, ground temperature 25°C, soil thermal resistivity 1.0 K·m/W, burial depth 0.8m.

In Air Installation (Solid Bonded Sheath)

Conductor Size (mm²)Flat Touching (A)Flat Spaced (A)Trefoil Touching (A)Trefoil Spaced (A)Enclosed (A)
35182211168178125
50216251201213150
70269308251266184
95323368302321219
120370420348370257
150413468393419288
185471525448478325
240548602525561376
300617670598639438
400701750687735497
500787831782837558
630877911886948624
800986101410081082727

Underground Installation (Solid Bonded Sheath)

Conductor Size (mm²)Direct Buried Flat Touching (A)Direct Buried Flat Spaced (A)Direct Buried Trefoil (A)Duct Flat Touching (A)Duct Flat Spaced (A)Duct Trefoil (A)Single Duct (A)
35177179174156156154140
50208208204181180180167
70251248249216212217204
95297291296253246256242
120334325336284274289279
150370356374314300322311
185412392420347328359350
240467439482391365410402
300516478538431397457462
400571522605474431510519
500627565674520466568580
630683607746560496520642
800740651822616537693734

Reference conditions per IEC 60287: ground temp 25°C, soil resistivity 1.0 K·m/W, burial depth 0.8m, single circuit.

Single-Point Bonded Sheath (Higher Ratings)

When single-point bonding eliminates circulating sheath currents, current ratings increase by 10–15% for smaller sizes and up to 35% for larger sizes. Key values for copper conductor, trefoil direct buried:

Conductor Size (mm²)Solid Bond Trefoil (A)Single-Point Bond Trefoil (A)Increase (%)
95296339+15%
150374430+15%
240482559+16%
300538626+16%
400605705+17%
500674788+17%
630746875+17%
800822961+17%

Single-Core 6.35/11kV Current Ratings — Aluminium Conductor (Amperes)

Aluminium conductors carry approximately 78% of the current of an equivalent copper conductor (based on conductivity ratio). For the same ampacity, aluminium requires roughly 1.6× the cross-sectional area of copper.

Underground Direct Buried — Trefoil Formation (Solid Bonded)

Conductor Size (mm²)Copper (A)Aluminium (A)Al/Cu Ratio
3517413477%
5020415978%
7024919478%
9529623178%
12033626278%
15037429278%
18542032978%
24048238079%
30053842779%
40060548580%
50067455082%
63074661983%
80082269184%

11kV Three-Core Cable Size Chart

Three-core 11kV cables are the standard choice for distribution feeders up to approximately 300mm² conductor size. They offer simpler installation (one cable pull instead of three), no sheath bonding requirements, and natural electromagnetic balance between phases.

Three-Core 6.35/11kV — Copper Conductor, XLPE, Copper Tape Screen, SWA, PVC Sheath

Standard construction: 3× [Cu conductor (Class 2) / semi-conductive screen / XLPE insulation (3.4mm) / semi-conductive screen / copper tape screen] / PVC bedding / galvanised steel wire armour / PVC outer sheath.

Conductor Size (mm²)Insulation Thickness (mm)Approx. Overall Diameter (mm)Approx. Weight (kg/km)Current Rating — Direct Buried (A)Current Rating — In Air (A)
353.4483200171164
503.4523800201195
703.4574600245241
953.4625600292291
1203.4676600330334
1503.4727800367375
1853.4779200412426
2403.48411500469495
3003.49013800521556
4003.49817000579629

Current ratings: direct buried in trefoil at 0.8m depth, 25°C ground temp, 1.0 K·m/W; in air = trefoil touching, 40°C ambient.

Three-Core 6.35/11kV — Aluminium Conductor, XLPE, Copper Tape Screen, SWA, PVC Sheath

Conductor Size (mm²)Approx. Overall Diameter (mm)Approx. Weight (kg/km)Current Rating — Direct Buried (A)Current Rating — In Air (A)
35482500133127
50522900157152
70573500191188
95624200227227
120674900257260
150725700287293
185776700323334
240848400372391
3009010000416443
4009812500469508

Weight reduction vs copper: approximately 30–40% depending on size. Same overall diameter because armour and sheathing dimensions remain unchanged.

11kV Cable Size Selection Guide

Selecting the correct 11kV cable size requires matching the cable's de-rated current capacity to the circuit's maximum demand current, while accounting for installation conditions that differ from the reference conditions used in standard rating tables.

Step-by-Step Selection Process

  1. Determine maximum demand current (I_B) — from transformer rating, motor starting current, or load study
  2. Select installation method — direct buried, in ducts, in air (determines base current rating table)
  3. Apply derating factors for actual conditions (see table below)
  4. Calculate required cable rating: I_Z ≥ I_B / (k₁ × k₂ × k₃ × k₄)
  5. Check voltage drop — typically ≤5% at full load for distribution circuits
  6. Verify short-circuit withstand — conductor must survive maximum fault current × clearance time

Derating Factors (Correction Factors per IEC 60287)

Ground Temperature Correction (Reference: 25°C)

Actual Ground Temp (°C)Correction Factor
151.07
201.04
251.00
300.96
350.92
400.88
450.83
500.78

Soil Thermal Resistivity Correction (Reference: 1.0 K·m/W)

Soil Resistivity (K·m/W)Correction Factor
0.51.17
0.71.10
1.01.00
1.50.89
2.00.81
2.50.75
3.00.70

Burial Depth Correction (Reference: 0.8m)

Actual Depth (m)Correction Factor
0.51.04
0.81.00
1.00.98
1.250.96
1.50.93
2.00.90

Grouping (Multiple Circuits) Correction — Direct Buried Trefoil

Number of CircuitsSpacing = 0 (touching)Spacing = 0.25mSpacing = 0.5mSpacing = 1.0m
20.800.850.900.95
30.700.760.820.88
40.640.700.770.84
60.560.630.700.78

Worked Example: 11kV Cable Size Selection

Project: 2 MVA transformer incoming cable, 200m route length, direct buried in tropical climate.

Step 1 — Maximum demand current: I_B = S / (√3 × U) = 2,000,000 / (1.732 × 11,000) = 105 A

Step 2 — Installation conditions:

  • Direct buried in trefoil, depth 1.0m
  • Ground temperature: 35°C (tropical)
  • Soil resistivity: 1.5 K·m/W (dry sandy soil)
  • Single circuit

Step 3 — Combined derating factor: k = 0.92 × 0.89 × 0.98 = 0.802

Step 4 — Required cable rating: I_Z ≥ 105 / 0.802 = 131 A

Step 5 — Select from 3-core table (copper, direct buried):

  • 50mm² = 201A ✓ (adequate)
  • 35mm² = 171A ✓ (adequate but check voltage drop)

Step 6 — Voltage drop check at 105A over 200m: For 3×50mm² Cu: ΔV ≈ (√3 × 105 × 0.2 × 0.495) = 18V = 0.16% of 11kV ✓

Result: 3×50mm² copper XLPE/SWA cable is suitable. The 95mm² size would be needed only if future load growth to 5 MVA is anticipated.

Short-Circuit Withstand Capacity

The conductor must survive the maximum prospective fault current for the protection clearance time without exceeding 250°C (XLPE insulation limit). The adiabatic equation per IEC 60949:

I²t = k² × S²

Where:

  • I = short-circuit current (A)
  • t = fault clearance time (s)
  • k = material constant (copper = 143, aluminium = 94 for XLPE insulation at 90°C initial temp)
  • S = conductor cross-section (mm²)

Maximum 1-Second Short-Circuit Current by Conductor Size

Conductor Size (mm²)Copper — 1s (kA)Copper — 3s (kA)Aluminium — 1s (kA)Aluminium — 3s (kA)
355.02.93.31.9
507.24.14.72.7
7010.05.86.63.8
9513.67.88.95.2
12017.29.911.36.5
15021.512.414.18.1
18526.515.317.410.0
24034.319.822.613.0
30042.924.828.216.3
40057.233.037.621.7
50071.541.347.027.1
63090.152.059.234.2
800114.466.175.243.4

Note: The metallic screen must also withstand fault current. Screen cross-section is selected based on the maximum earth fault current and protection clearance time at the installation location.

Screen Fault Rating

For copper wire screens, the 1-second fault withstand capacity:

Screen Cross-Section (mm²)1-Second Rating (kA)
162.3
253.6
355.0
507.2
7010.0
9513.6

Select screen size so that: Screen fault rating ≥ maximum earth fault current at that point in the network.

Installation Requirements

Minimum Bending Radius

The minimum bending radius prevents mechanical damage to insulation and screens during installation.

Cable TypeMinimum Bend Radius
Single-core, unarmoured15× overall diameter
Single-core, armoured (SWA)15× overall diameter
Three-core, armoured (SWA)12× overall diameter
Three-core, unarmoured12× overall diameter

Practical examples:

  • 3×240mm² SWA (OD ≈ 84mm): minimum bend radius = 84 × 12 = 1008mm ≈ 1.0m
  • 1×400mm² unarmoured (OD ≈ 44.5mm): minimum bend radius = 44.5 × 15 = 668mm ≈ 0.67m

Maximum Pulling Tension

Conductor MaterialMaximum Tension
Copper50 N/mm² × conductor area
Aluminium30 N/mm² × conductor area

Example: 3×300mm² Cu cable maximum pulling tension = 50 × 300 = 15,000 N = 15 kN (per core, applied via pulling eye on all three conductors simultaneously = 45 kN total).

Underground Installation Depth

Installation ScenarioMinimum Cover (typical)
Footpath0.45m
Road crossing0.60m
Agricultural land0.90m
Under building0.60m
With protective tilesDepth may be reduced by 0.1m

Note: Actual minimum cover varies by country and utility specification. Always check local regulations.

6.35/11kV vs 8.7/15kV — Which Rating for Your 11kV Network?

Both voltage ratings serve 11kV systems, but they are not interchangeable without understanding the earthing system:

Parameter6.35/11kV8.7/15kV
System earthingSolidly earthed or low-impedance earthedImpedance earthed, isolated neutral, or resonant earthed
Earth fault clearanceWithin 1 hour (typically less than 1s)May persist for hours
Insulation thickness (IEC 60502-2)3.4 mm4.5 mm
Overall diameter (3×240mm² SWA, approx.)84 mm92 mm
Weight (3×240mm² SWA, approx.)11,500 kg/km13,200 kg/km
Cost premium (8.7/15kV over 6.35/11kV)+12–18%
Typical marketsUK, Australia, Middle East, Africa, IndiaContinental Europe (some networks), industrial isolated systems
Standard referencesBS 6622, AS/NZS 1429.1BS 6622 Category B, NF C 33-226

Recommendation: If you are unsure which rating to specify, check the Distribution Network Operator (DNO) approved cable schedule for your region. Most 11kV distribution networks globally are solidly earthed, making 6.35/11kV the correct choice. Specifying 8.7/15kV "to be safe" adds unnecessary cost and installation difficulty without improving reliability on a solidly-earthed network.

Copper vs Aluminium — Size Equivalence Table

When converting between copper and aluminium for the same circuit rating:

Required Current (A)Copper Size (mm²)Aluminium Size (mm²)Weight Saving (Al vs Cu)Cost Saving (typical)
~170355025%30–40%
~200507028%32–42%
~250709528%33–43%
~2959512030%35–45%
~33512015030%35–45%
~37515018532%38–48%
~42018524033%38–48%
~48024030035%40–50%
~54030040035%40–50%
~60540050038%42–52%

When to choose aluminium:

  • Long route lengths where weight reduction eases installation
  • Cost-sensitive projects where lifetime performance is acceptable
  • Utility distribution feeders (most DNOs accept aluminium for 11kV)
  • Non-corrosive environments

When to choose copper:

  • Limited duct or trench space (copper is smaller for same rating)
  • High fault-level locations (copper withstands more fault current per mm²)
  • Corrosive or subsea environments
  • Short cable routes where material cost difference is minimal
  • Industrial sites with high ambient temperatures (copper's higher melting point provides margin)

Common 11kV Cable Applications

ApplicationTypical Cable ConfigurationCommon Sizes
Utility primary distribution feeder3-core Al, XLPE/SWA185–300mm²
Ring main unit (RMU) interconnection3-core Al or Cu, XLPE/SWA95–185mm²
Transformer incoming supply (1–5 MVA)3-core Cu, XLPE/SWA50–150mm²
Transformer incoming supply (5–20 MVA)Single-core Cu, XLPE/Cu screen240–500mm²
Solar farm collection circuitSingle-core Al, XLPE185–400mm²
Wind farm inter-array3-core Cu/Al, XLPE/SWA95–240mm²
Mining site reticulation3-core Cu, XLPE/SWA (EPR for flexibility)70–185mm²
Industrial plant internal MV distribution3-core Cu, XLPE/SWA or unarmoured95–300mm²
DNO last-mile connection3-core Al, XLPE/SWA185–300mm² (standard)

Frequently Asked Questions

What is the maximum current for 240mm² 11kV cable?

For a 3-core 240mm² copper XLPE/SWA cable at 6.35/11kV, rated per IEC 60502-2 reference conditions:

  • Direct buried (trefoil): 469 A
  • In air (trefoil touching): 495 A

For single-core 240mm² copper, direct buried trefoil (solid bonded): 482 A

These are base ratings. Apply derating factors for actual ground temperature, soil resistivity, burial depth, and circuit grouping.

What is the outer diameter of 11kV 3-core 185mm² cable?

Approximately 77mm for copper conductor XLPE/SWA construction at 6.35/11kV. This gives a minimum bending radius of approximately 924mm (12× OD). Allow sufficient space in cable trays, ducts, and joint bays.

What size 11kV cable do I need for a 5 MVA transformer?

Full load current: I = 5,000,000 / (1.732 × 11,000) = 262 A

For a single circuit, direct buried in temperate climate (25°C ground, 1.0 K·m/W soil):

  • 3-core 95mm² copper (292A rated) — adequate with minimal margin
  • 3-core 120mm² copper (330A rated) — recommended for load growth allowance
  • 3-core 150mm² aluminium (287A rated) — adequate if using aluminium

For tropical or harsh conditions, add derating: 120mm² Cu or 185mm² Al is the typical choice.

Can I use 11kV cable for a 10kV system?

Yes. Cable rated 6.35/11kV has a maximum system voltage (Um) of 12kV, which covers 10kV systems. The Chinese standard GB/T 12706.2 rates these cables as 6/10kV or 8.7/10kV depending on the earthing arrangement. Electrically identical to IEC 60502-2 6.35/11kV cable — different labelling convention.

What is the insulation resistance of 11kV XLPE cable?

XLPE insulation resistance is typically >5000 MΩ·km at 20°C for new cable. IEC 60502-2 does not specify a minimum insulation resistance value for XLPE cables (it's inherently high). Instead, the standard requires:

  • Routine voltage test: 21kV AC for 5 minutes (6.35/11kV rated cable)
  • Partial discharge: ≤10 pC at 1.73 × U₀ = 11kV
  • Type test: 42kV AC for 4 hours with heating cycles

How many years does 11kV XLPE cable last?

Design life per IEC 60502-2 is 30 years minimum under rated conditions. In practice, properly installed and operated XLPE 11kV cables routinely achieve 40+ years of service. Key factors affecting actual life:

  • Operating temperature (continuous operation near 90°C limit accelerates ageing)
  • Water ingress to insulation (water treeing)
  • Partial discharge activity
  • Mechanical damage during installation
  • Soil thermal conditions causing chronic overheating

Testing Requirements for 11kV Cable

Routine Tests (Every Drum)

Per IEC 60502-2 Clause 14:

TestRequirement
Conductor resistancePer IEC 60228 class tolerance
Voltage test21 kV AC for 5 minutes (6.35/11kV)
Partial discharge≤10 pC at 1.73 × U₀
Insulation thickness measurementPer Table 1 minimum at any point
Dimensional checkConductor diameter, overall diameter

Type Tests (Design Qualification)

TestRequirement
Bending test + partial dischargeAfter bending at minimum radius
Heating cycle voltage test42 kV for 4 hours, 20 cycles at conductor temp cycling 5–90°C
Impulse voltage test75 kV (BIL) for 6.35/11kV
Hot set testXLPE elongation/set at 200°C
Shrinkage testInsulation and sheath materials
Water penetrationLongitudinal and radial (if claimed)

Sample Tests

TestRequirement
Conductor tensile/elongationPer IEC 60228
Insulation tensile/elongationBefore and after ageing at 135°C
Sheath tensile/elongationBefore and after ageing
Hot pressure test80°C for PVC, specific deformation limits
Carbon black content (PE sheath)2.5 ± 0.5%
Ozone resistance (EPR only)No cracking

Applicable International Standards

StandardScope
IEC 60502-2Power cables 6kV to 30kV — construction, testing, dimensions
IEC 60228Conductor requirements (Class 1, 2, 5, 6)
IEC 60287Current rating calculations (steady-state)
IEC 60949Short-circuit temperature rise calculations
IEC 60840Power cables above 30kV (for 33kV and above)
BS 6622UK standard for MV XLPE cables 6.35/11kV and 19/33kV
BS 7870-4UK distribution cables with integrated services
AS/NZS 1429.1Australian/NZ standard for MV polymeric cables
GB/T 12706.2Chinese standard for MV power cables (equivalent to IEC 60502-2)
NF C 33-226French standard for MV cables

11kV Cable from China: Factory-Direct Supply

We manufacture the complete range of 6.35/11kV and 8.7/15kV XLPE cables at our ISO 9001 certified factory in Henan, China. Our 11kV cable production capabilities include:

Product range:

  • Single-core: 35mm² to 800mm², copper or aluminium
  • Three-core: 35mm² to 400mm², copper or aluminium
  • Armour options: steel wire armour (SWA), steel tape armour (STA), or unarmoured
  • Screen types: copper tape, copper wire, or combined copper wire/tape
  • Sheath: PVC, PE, MDPE, or LSZH (low smoke zero halogen)

Standards compliance:

  • IEC 60502-2 (international)
  • GB/T 12706.2 (China national standard)
  • BS 6622 (UK market)
  • AS/NZS 1429.1 (Australia/NZ market)
  • NF C 33-226 (French market)

Testing capability:

  • Full routine testing per IEC 60502-2 on every production drum
  • Type testing at accredited third-party laboratories (KEMA, CNAS-accredited labs)
  • Partial discharge measurement system (sensitivity better than 5 pC)
  • VLF and AC withstand testing for commissioning support

Quality certifications:

  • ISO 9001:2015 quality management
  • ISO 14001:2015 environmental management
  • CCC (China Compulsory Certification)
  • PCCC (China Power Cable Product Certification)
  • KEMA type-tested designs

Whether you need 500 meters for a single transformer connection or 50 km for a distribution network expansion, we supply 11kV cable with full test reports, material certificates, and export documentation. Contact us for specifications and pricing.

Summary: Quick-Reference 11kV Cable Sizing Table

For rapid cable selection on standard projects (single circuit, direct buried trefoil, 25°C ground, 1.0 K·m/W soil):

Load (MVA at 11kV)Full Load Current (A)Minimum Cu Size (3-core)Minimum Al Size (3-core)Recommended Size (with margin)
15235mm²35mm²50mm² Cu / 70mm² Al
210535mm²50mm²70mm² Cu / 95mm² Al
315750mm²70mm²95mm² Cu / 120mm² Al
526295mm²150mm²120mm² Cu / 185mm² Al
7.5394185mm²240mm²240mm² Cu / 300mm² Al
10525300mm²400mm²400mm² Cu / single-core
15787Single-core req'dSingle-core req'd1×400mm² Cu or 1×500mm² Al
201050Single-core req'dSingle-core req'd1×630mm² Cu or 1×800mm² Al

This quick-reference assumes standard conditions and no derating. For actual projects, always apply correction factors for ground temperature, soil resistivity, depth, and grouping as shown in the selection guide above.

Need a Quotation?

Contact our team for competitive factory-direct pricing, MOQ details, and delivery schedules.