China Cable Factory

Cable Size Chart & Current Rating Table — mm² to AWG, Amps by Size

· 23 min read· China Cable Factory

Key Takeaway

Find the right cable size fast. Full current rating tables (IEC 60364), mm² to AWG conversion, voltage drop data, and derating factors. Copper & aluminium, 1.5mm² to 1000mm². Backed by 20+ years of cable manufacturing experience.

Selecting the correct cable size is the single most critical decision in any electrical installation. Undersized cable overheats, trips breakers, causes voltage drop problems, and creates fire hazards. Oversized cable wastes money — copper and aluminium are expensive materials. This guide gives you everything you need to size cables correctly: complete mm² to AWG conversion tables, current rating charts for both copper and aluminium conductors, voltage drop calculations, and practical selection methods used by engineers worldwide.

Whether you are designing a power distribution network in Africa, wiring an industrial plant in Southeast Asia, or specifying cables for a construction project in the Middle East — the tables in this article will be your daily reference.

Cable cross-sections showing different sizes from 1.5mm² to 300mm² copper and aluminium conductors
Cable sizes range from 1.5mm² for lighting circuits to 1000mm² for high-current industrial feeders

Cable Size Chart: mm² Cross-Section Area (IEC Standard)

The international standard (IEC 60228) defines cable sizes by conductor cross-sectional area in square millimetres (mm²). This is the system used across Europe, Africa, Asia, Middle East, and most of the world outside North America.

Standard IEC Cable Sizes

The preferred sizes per IEC 60228 are:

Small sizes (lighting, control, instrumentation): 0.5 — 0.75 — 1.0 — 1.5 — 2.5 — 4 — 6 — 10 mm²

Medium sizes (power distribution, motors): 16 — 25 — 35 — 50 — 70 — 95 — 120 mm²

Large sizes (main feeders, transmission): 150 — 185 — 240 — 300 — 400 — 500 — 630 — 800 — 1000 mm²

These are nominal sizes — the actual measured cross-section may vary slightly due to conductor construction (solid vs stranded) and manufacturing tolerances (IEC 60228 allows up to +2% resistance tolerance).

mm² to AWG Conversion Chart

North America uses the American Wire Gauge (AWG) and kcmil system instead of mm². If you are working with equipment rated in AWG or sourcing cable for projects that specify AWG, use this conversion table:

AWG/kcmilmm² (exact)mm² (nearest IEC)Conductor Ø (mm)Typical Use
18 AWG0.8230.751.02Thermostat, signal wire
16 AWG1.311.51.29Light fixtures, extension cords
14 AWG2.082.51.6315A branch circuits
12 AWG3.3142.0520A branch circuits
10 AWG5.2662.5930A circuits, dryers
8 AWG8.37103.2640A circuits, ranges
6 AWG13.3164.1155A, large appliances
4 AWG21.2255.1970A feeders
2 AWG33.6356.5495A feeders
1 AWG42.4507.35110A feeders
1/0 (0) AWG53.5508.25125A service entrance
2/0 (00) AWG67.4709.27145A service entrance
3/0 (000) AWG85.09510.40165A feeders
4/0 (0000) AWG107.212011.68195A main feeders
250 kcmil12712012.70215A
350 kcmil17718515.02260A
500 kcmil25324017.96320A
750 kcmil38040022.00400A
1000 kcmil50750025.43475A

Key conversion formula:

Important note: AWG and mm² sizes do not align exactly. When substituting, always use the next larger IEC size to ensure adequate current capacity. For example, 6 AWG (13.3mm²) should be replaced with 16mm², not 10mm².

Cable Current Rating Chart — Copper Conductors

Current ratings (ampacity) depend on insulation type, installation method, ambient temperature, and grouping. The following tables are based on IEC 60364-5-52 (equivalent to BS 7671) reference conditions.

Single-Core Copper Cable — Current Ratings by Installation Method

Reference conditions: 30°C ambient air, 20°C ground temperature, thermal resistivity of soil 2.5 K·m/W.

Size (mm²)Method A1: Enclosed in Conduit in Wall (A)Method B1: Enclosed in Conduit on Wall (A)Method C: Clipped Direct (A)Method D: Direct Buried (A)Method E: Free Air (A)
1.514.517.519.52223
2.52024272931
42632363742
63441464754
104657636375
1661768581100
2580101112104133
3599125138125164
50119151168148198
70151192213183253
95182232258216306
120210269299246354
150240309344278407
185273353392312464
240321415461361546
300367480530408628
400438569634478749
500502652729540860
630578752843614993

Three-Core/Four-Core Copper Cable — Current Ratings

For multicore cables (3-core or 4-core), ratings are lower due to mutual heating between conductors.

Size (mm²)3/4-Core in Conduit in Wall (A)3/4-Core Clipped Direct (A)3/4-Core Direct Buried (A)3/4-Core in Free Air (A)
1.51317.51816.5
2.517.5242423
423323030
629413838
1039575152
1652766669
2568968390
358311999111
5099144118133
70125184149171
95150223179207
120172259206240
150196299225275
185223341257314
240261403300370
300298464340426
400351552398507
500401640453583

Installation method definitions:

Cable Current Rating Chart — Aluminium Conductors

Aluminium has approximately 61% the conductivity of copper. For the same current, aluminium cable needs a larger cross-section — typically 1.6× the copper area.

Size (mm²)Al Single-Core Clipped Direct (A)Al Single-Core Free Air (A)Al 3/4-Core Clipped Direct (A)Al 3/4-Core Direct Buried (A)
1665785752
25841017466
351041269280
5012515411095
70160198140120
95195241170145
120226280197167
150261324227192
185298371259219
240352440305258
300406508351296
400483607419349
500557701484401

Copper vs Aluminium — quick equivalents for project budgeting:

Copper SizeEquivalent Aluminium SizeCurrent Rating (approx.)
10mm² Cu16mm² Al~63A
16mm² Cu25mm² Al~85A
25mm² Cu35mm² Al~110A
35mm² Cu50mm² Al~130A
50mm² Cu70mm² Al~165A
70mm² Cu95mm² Al~200A
95mm² Cu120mm² Al~240A
120mm² Cu150mm² Al~275A
150mm² Cu185mm² Al~315A
185mm² Cu240mm² Al~365A
240mm² Cu300mm² Al~430A
300mm² Cu400mm² Al~500A

Voltage Drop Calculation & Cable Sizing

Current rating alone does not determine cable size. For long cable runs, voltage drop often becomes the controlling factor — especially in Africa, Southeast Asia, and rural electrification projects where distribution distances are long.

Maximum Allowable Voltage Drop

StandardLighting CircuitsPower CircuitsTotal (Source to Load)
IEC 603643%5%4–6% recommended
BS 7671 (UK)3%5%
NEC (USA)3% recommended5% recommended
AS/NZS 3008 (Australia)5%5%7% max
South Africa (SANS 10142)5%5%

Voltage Drop Formula

For AC single-phase circuits: Vd = 2 × I × L × (R·cosφ + X·sinφ) / 1000

For AC three-phase circuits: Vd = √3 × I × L × (R·cosφ + X·sinφ) / 1000

Where:

Voltage Drop Table — Copper Cable (mV/A/m)

This table gives voltage drop per ampere per metre for copper cables at 70°C conductor temperature, power factor 0.8:

Size (mm²)2-Core/Single Phase (mV/A/m)3/4-Core Three Phase (mV/A/m)
1.52925
2.51815
4119.5
67.36.4
104.43.8
162.82.4
251.751.50
351.251.10
500.930.80
700.630.55
950.460.40
1200.360.31
1500.290.25
1850.240.21
2400.1850.160
3000.1500.130

Practical Example — Sizing by Voltage Drop

Project: 3-phase motor, 45kW, 400V, power factor 0.85, cable run 120 metres, installed in conduit on wall.

Step 1: Calculate current I = 45,000 / (√3 × 400 × 0.85) = 76.5A

Step 2: Select cable by current rating From the current rating table (Method B1, 3-core): 25mm² carries 101A ✓

Step 3: Check voltage drop Using mV/A/m table: 25mm² three-phase = 1.50 mV/A/m Vd = 76.5 × 120 × 1.50 / 1000 = 13.8V Percentage: 13.8 / 400 × 100 = 3.4% ✓ (under 5% limit)

Result: 25mm² copper cable is adequate for both current and voltage drop.

If the run was 250 metres: Vd = 76.5 × 250 × 1.50 / 1000 = 28.7V = 7.2% ✗ (exceeds 5%) Need to upsize to 35mm²: Vd = 76.5 × 250 × 1.10 / 1000 = 21.0V = 5.3% — still borderline Upsize to 50mm²: Vd = 76.5 × 250 × 0.80 / 1000 = 15.3V = 3.8% ✓

This demonstrates why long cable runs in industrial and infrastructure projects often require larger sizes than current rating alone would suggest.

Cable Size Selection by Load (kW)

For quick reference, here is a cable size guide based on load power for common voltages:

Three-Phase 400V System — Copper Cable

Load (kW)Current (A) at PF 0.85Min. Size — Short Run <30mMin. Size — Medium Run 30–100mMin. Size — Long Run 100–300m
35.11.5mm²2.5mm²4mm²
5.59.31.5mm²2.5mm²4mm²
7.512.72.5mm²4mm²6mm²
1118.72.5mm²4mm²10mm²
1525.54mm²6mm²16mm²
2237.36mm²10mm²25mm²
3050.910mm²16mm²35mm²
3762.810mm²25mm²50mm²
4576.416mm²25mm²50mm²
5593.425mm²35mm²70mm²
75127.335mm²50mm²95mm²
90152.850mm²70mm²120mm²
110186.750mm²95mm²150mm²
132224.170mm²120mm²185mm²
160271.695mm²150mm²240mm²
200339.5120mm²185mm²300mm²
250424.4150mm²240mm²400mm²
315534.7185mm²300mm²2×185mm²
400679.0240mm²400mm²2×240mm²
500848.8300mm²2×240mm²2×300mm²

Single-Phase 230V System — Copper Cable

Load (kW)Current (A) at PF 1.0Min. Size — Short Run <20mMin. Size — Medium Run 20–50mMin. Size — Long Run 50–100m
14.31.5mm²1.5mm²2.5mm²
28.71.5mm²2.5mm²4mm²
313.01.5mm²2.5mm²6mm²
4.519.62.5mm²4mm²10mm²
626.14mm²6mm²10mm²
834.86mm²10mm²16mm²
1043.510mm²16mm²25mm²
1252.210mm²16mm²25mm²
1565.216mm²25mm²35mm²

Important: These tables assume standard installation conditions (30°C ambient, single circuit, no grouping). Apply derating factors for hot climates, grouped cables, or thermal insulation proximity.

Derating Factors: When Standard Ratings Don't Apply

Real-world installations rarely match reference conditions perfectly. Apply these correction factors to the standard current ratings:

Ambient Temperature Correction (Air)

Ambient Temp (°C)PVC Insulation (70°C rated)XLPE Insulation (90°C rated)
251.061.04
301.001.00
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.500.71

Critical for hot climates: In regions where ambient temperatures regularly exceed 40°C (Middle East, sub-Saharan Africa, South Asia), you must derate cable current capacity. A cable rated 100A at 30°C ambient only carries 87A at 40°C with PVC insulation. This is why XLPE insulation is strongly preferred for hot climate installations — it loses less capacity at elevated temperatures.

Grouping Correction Factors

When multiple cables run together, mutual heating reduces each cable's capacity:

Number of Grouped CircuitsBunched in ConduitSingle Layer on Wall/TraySingle Layer Touching
11.001.001.00
20.800.880.85
30.700.820.79
40.650.770.75
50.600.750.73
60.570.730.72
90.500.690.69
120.450.680.68

Soil Temperature & Thermal Resistivity Correction (Buried Cables)

Soil Temp (°C)Correction Factor (PVC)Correction Factor (XLPE)
151.071.04
201.001.00
250.930.96
300.850.93
350.760.89
400.670.85
Soil Thermal Resistivity (K·m/W)Correction FactorTypical Condition
1.01.18Very wet soil
1.51.10Wet soil
2.51.00Reference (damp)
3.00.96Dry soil
5.00.84Very dry/sandy soil

Cable Construction: How Size Relates to Physical Dimensions

Cable cross-section is just the conductor area. The overall cable diameter depends on insulation thickness, armouring, and sheath:

Typical Overall Dimensions — 4-Core Armoured XLPE Cable (0.6/1kV)

Conductor Size (mm²)Conductor Ø (mm)Insulation Thickness (mm)Armour TypeOverall Ø (mm)Weight (kg/km)
4 × 62.80.7STA23640
4 × 103.60.7STA26880
4 × 164.50.7STA291,150
4 × 255.60.9SWA351,700
4 × 356.70.9SWA382,150
4 × 508.01.0SWA422,800
4 × 709.41.1SWA473,700
4 × 9511.01.1SWA524,750
4 × 12012.41.2SWA575,850
4 × 15013.81.4SWA617,000
4 × 18515.31.6SWA668,400
4 × 24017.51.7SWA7310,600
4 × 30019.51.8SWA7912,800
4 × 40022.62.0SWA8716,200

Why this matters for procurement:

Short-Circuit Current Rating

Cable must also withstand short-circuit current without damage. The adiabatic equation determines the minimum cable size for fault protection:

Minimum size = I²t / k²

Where:

Maximum Short-Circuit Current by Cable Size (1 Second Duration)

Size (mm²)Copper/PVC (kA for 1s)Copper/XLPE (kA for 1s)Aluminium/PVC (kA for 1s)Aluminium/XLPE (kA for 1s)
40.460.570.300.38
60.690.860.460.56
101.151.430.760.94
161.842.291.221.50
252.883.581.902.35
354.035.012.663.29
505.757.153.804.70
708.0510.015.326.58
9510.9313.597.228.93
12013.8017.169.1211.28
15017.2521.4511.4014.10
18521.2826.4614.0617.39
24027.6034.3218.2422.56
30034.5042.9022.8028.20

Cable Sizing Checklist for Engineers

Use this systematic approach for every cable sizing decision:

Step 1: Determine design current (IB)

Step 2: Select protective device rating (IN)

Step 3: Select cable size for current capacity (IZ)

Step 4: Verify voltage drop

Step 5: Verify short-circuit rating

Step 6: Verify earth fault loop impedance

Final size = largest of Step 3, 4, 5, and 6 results

Frequently Asked Questions

What size cable do I need for 100 amps?

For 100A in a three-phase system: 25mm² copper (clipped direct) or 35mm² aluminium. If installed in conduit in wall, you need 35mm² copper. Always verify voltage drop for runs over 30 metres.

How do I convert AWG to mm²?

The most common conversions: 14 AWG ≈ 2.5mm², 12 AWG ≈ 4mm², 10 AWG ≈ 6mm², 8 AWG ≈ 10mm², 6 AWG ≈ 16mm², 4 AWG ≈ 25mm², 2 AWG ≈ 35mm², 1/0 AWG ≈ 50mm², 4/0 AWG ≈ 120mm². Always round UP to the next IEC size when substituting.

Is 4mm cable OK for a 32A circuit?

No. 4mm² copper in conduit in wall (Method A1) is only rated 26A — below the 32A protective device rating. You need 6mm² minimum (rated 34A in the same condition). This is a common mistake that causes cable overheating.

What is the difference between cable size and wire gauge?

Cable size (mm²) describes the cross-sectional area of the conductor — it directly tells you the amount of conducting material. Wire gauge (AWG) is an arbitrary numbering system where smaller numbers mean larger wires. mm² is the international standard (IEC); AWG is used in North America.

How does cable length affect size selection?

Longer cables have more resistance, causing greater voltage drop. For short runs (under 20m), current rating alone usually determines size. For runs over 50m, voltage drop almost always forces you to use a larger cable than current alone requires. A 50m run may need one size up; a 200m run may need two or three sizes up.

Why use XLPE insulation instead of PVC for larger cables?

XLPE-insulated cables have a higher continuous operating temperature (90°C vs 70°C for PVC), which means approximately 15–20% more current capacity at the same conductor size. For cables 50mm² and above, the additional capacity of XLPE often allows you to use a smaller conductor — saving material cost that more than offsets the slightly higher insulation cost.

What cable size for a 200m run at 50A?

At 50A over 200m three-phase (400V), using mV/A/m method:

For single-phase 230V at the same distance: you would likely need 70mm² due to higher voltage drop percentage.

Related Products & Resources

Cable Products for Your Project

Related Technical Guides

Get the Right Cable for Your Project

Need help selecting cable sizes for your project? Send us your load schedule or single-line diagram and our engineering team will provide:

We manufacture all standard sizes from 1.5mm² to 1000mm² in copper and aluminium, with PVC or XLPE insulation, armoured or unarmoured. IEC 60502, BS 5467, and GB/T 12706 certified.

Need a Quotation?

Contact our team for competitive factory-direct pricing, MOQ details, and delivery schedules.